CVE-2026-1773
High 7.5 CVSS 3.1
Description
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Description as published by the source, in English.
Key facts
- Published
- 2026-02-24
- Last modified
- 2026-06-17
- Assigned by
- cybersecurity@hitachienergy.com
- CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H- Scored by
- nvd@nist.gov (NVD Primary)
- Probability of exploitation
-
0.4 %
higher than 34 %
of all known vulnerabilities
EPSS, next 30 days, model v2026.06.15 - Fix available
- Not registered in the sources
Affected products
| Vendor | Product | Versions | Status |
|---|---|---|---|
| Hitachienergy | Rtu520 | all versions listed | Not affected |
| Hitachienergy | Rtu520 Firmware | 13.8.1 | Affected |
| Hitachienergy | Rtu520 Firmware | ≥ 12.7.1, ≤ 12.7.7 | Affected |
| Hitachienergy | Rtu520 Firmware | ≥ 13.5.1, ≤ 13.5.4 | Affected |
| Hitachienergy | Rtu520 Firmware | ≥ 13.6.1, ≤ 13.6.2 | Affected |
| Hitachienergy | Rtu520 Firmware | ≥ 13.7.1, < 13.7.8 | Affected |
| Hitachienergy | Rtu530 | all versions listed | Not affected |
| Hitachienergy | Rtu530 Firmware | 13.8.1 | Affected |
| Hitachienergy | Rtu530 Firmware | ≥ 12.7.1, ≤ 12.7.7 | Affected |
| Hitachienergy | Rtu530 Firmware | ≥ 13.5.1, ≤ 13.5.4 | Affected |
| Hitachienergy | Rtu530 Firmware | ≥ 13.6.1, ≤ 13.6.2 | Affected |
| Hitachienergy | Rtu530 Firmware | ≥ 13.7.1, < 13.7.8 | Affected |
| Hitachienergy | Rtu540 | all versions listed | Not affected |
| Hitachienergy | Rtu540 Firmware | 13.8.1 | Affected |
| Hitachienergy | Rtu540 Firmware | ≥ 12.7.1, ≤ 12.7.7 | Affected |
| Hitachienergy | Rtu540 Firmware | ≥ 13.5.1, ≤ 13.5.4 | Affected |
| Hitachienergy | Rtu540 Firmware | ≥ 13.6.1, ≤ 13.6.2 | Affected |
| Hitachienergy | Rtu540 Firmware | ≥ 13.7.1, < 13.7.8 | Affected |
| Hitachienergy | Rtu560 | all versions listed | Not affected |
| Hitachienergy | Rtu560 Firmware | 13.8.1 | Affected |
| Hitachienergy | Rtu560 Firmware | ≥ 12.7.1, ≤ 12.7.7 | Affected |
| Hitachienergy | Rtu560 Firmware | ≥ 13.5.1, ≤ 13.5.4 | Affected |
| Hitachienergy | Rtu560 Firmware | ≥ 13.6.1, ≤ 13.6.2 | Affected |
| Hitachienergy | Rtu560 Firmware | ≥ 13.7.1, < 13.7.8 | Affected |
Weakness type
-
CWE-184: Incomplete List of Disallowed Inputs
The product implements a protection mechanism that relies on a list of inputs (or properties of inputs) that are not allowed by policy or otherwise require other action to neutralize before additional processing takes p…
References
Does this affect you?
A vulnerability matters only if you run the product, in an affected version, somewhere an attacker can reach.