Inductive Automation Ignition Execution with Unnecessary Privileges

High 7.3 CVSS 4.0

Description

Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations. On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.

Description as published by the source, in English.

Key facts

Published
2025-12-18
Last modified
2026-08-27
Assigned by
icscert
CVSS vector
CVSS:4.0/AV:A/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Scored by
CVE Program
Probability of exploitation
0.2 % higher than 14 % of all known vulnerabilities
EPSS, next 30 days, model v2026.06.15
Fix available
Not registered in the sources

Affected products

Vendor Product Versions Status
Inductive Automation Ignition 8.1.x Affected
Inductive Automation Ignition 8.3.x Affected

Weakness type

  • CWE-250: Execution with Unnecessary Privileges

    The product performs an operation at a privilege level that is higher than the minimum level required, which creates new weaknesses or amplifies the consequences of other weaknesses.