Vulnerabilities

CVE-2023-2186

Critical 9.8 CVSS 3.1

Description

On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to the SCADA Data Gateway to perform unrestricted memory reads.An unauthenticated user can use this format string vulnerability to repeatedly crash the GTWWebMonitor.exe process to DoS the Web Monitor. Furthermore, an authenticated user can leverage this vulnerability to leak memory from the GTWWebMonitor.exe process. This could be leveraged in an exploit chain to gain code execution.

Description as published by the source, in English.

Key facts

Published
2023-06-07
Last modified
2026-10-23
Assigned by
trellixpsirt@trellix.com
CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Scored by
nvd@nist.gov (NVD Primary)
Probability of exploitation
0.7 % higher than 50 % of all known vulnerabilities
EPSS, next 30 days, model v2026.06.15
Fix available
Not registered in the sources

Affected products

Vendor Product Versions Status
Trianglemicroworks Scada Data Gateway ≤ 5.01.03 Affected

Weakness type

References

Does this affect you?

A vulnerability matters only if you run the product, in an affected version, somewhere an attacker can reach.